PERFORMANCE DATA & PRESSURE CURVES
5-1
SM SAFRPM 1-A.0 GB
5. PERFORMANCE DATA
5.1 SAF024 / OU7-24 Z R410A
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
7.01 7.26 7.43 7.61 7.72
SC
4.88 5.09 5.28 5.42 5.52
PI
1.68 1.68 1.69 1.69 1.70
20
(1)
TC
6.78 7.15 7.37 7.55 7.71
SC
4.78 5.04 5.25 5.40 5.50
PI
1.82 1.83 1.84 1.85 1.85
25
TC
6.42 6.93 7.28 7.50 7.69
SC
4.66 4.94 5.21 5.36 5.46
PI
1.97 1.99 2.00 2.01 2.03
30
TC
6.00 6.53 7.06 7.31 7.53
SC
4.51 4.79 5.10 5.25 5.35
PI
2.13 2.16
2.18
2.19 2.21
35
TC
5.56 6.03
6.65
6.98 7.31
SC
4.29 4.60 4.98 5.12 5.22
PI
2.29 2.33
2.37
2.39 2.40
40
TC
5.05 5.50
6.00
6.56 6.90
SC
4.04 4.35 4.71 4.86 4.96
PI
2.47 2.51 2.56 2.59 2.61
46
TC
4.38 4.79 5.27 5.82 6.27
SC
3.72 3.99 4.30 4.45 4.54
PI
2.70 2.74 2.81 2.85 2.88
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, Optional Accessories are needed.