DNG DC Inverter SeriesIndoor Units Outdoor UnitsDNG 50 DCI DCI 50DNG 60 DCI DCI 60DNG 72 DCIDCI 72DCI 72ZDNG 80 DCI DCI 80APRIL 2007REFRIGERANTR410A
2-3PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2.3 DNG72 DCI Model Indoor Unit DNG 72 DCIModel Outdoor Unit DCI 72 R410AInstallation Meth
2-4PRODUCT DATA SHEETRevision Y07-02 Service Manual - DNG DCI2.4 DNG72Z DCI Model Indoor Unit DNG 72 DCIModel Outdoor Unit DCI 72 Z R410AInstallation
2-5PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2.5 DNG80 DCI Model Indoor Unit DNG 80 DCIModel Outdoor Unit DCI 80 R410AInstallation Meth
3-1RATING CONDITIONS Revision Y07-02Service Manual - DNG DCI3. RATING CONDITIONSStandard conditions in accordance with
4-1OUTLINE DIMENSIONSRevision Y07-02Service Manual - DNG DCI4. OUTLINE DIMENSIONS4.1 Indoor Unit: DNG 50, 60, 72, 80Model A B C D E F G H I J K LDNG5
4-2OUTLINE DIMENSIONSRevision Y07-02 Service Manual - DNG DCI4.2 Outdoor Unit: DCI 504.3 Outdoor Unit: DCI 60CONTENT
4-3OUTLINE DIMENSIONSRevision Y07-02Service Manual - DNG DCI4.4 Outdoor Unit: DCI 72/80CONTENT
5-1PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5. PERFORMANCE DATA & PRESSURE CURVES5.1 DNG50 DCI / DCI 505.1.1
5-2PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.1.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL
5-3PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.1.5 Pressure Curves (Cooling – Test Mode) Discharge Pressure VS. Out
ALIST OF EFFECTIVE PAGESRevision Y07-02Service Manual - DNG DCILIST OF EFFECTIVE PAGESNote: Changes in the pages are indicated by a “Revision#” in th
5-4PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.1.6 Pressure Curves (Heating – Test Mode)Suction Pressure V
5-5PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.1.7 Capacity Correction Factor Due to Tubing Length Cooling Heating
5-6PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2 DNG60 DCI / DCI 605.2.1 Cooling Capacity (kW)ID COIL ENT
5-7PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.2.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING
5-8PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure
5-9PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.2.6 Pressure Curves (Heating – Test Mode)Suction Pressure VS.Outdoor
5-10PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2.7 Capacity Correction Factor Due to Tubing Length Cooli
5-11PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3 DNG72 DCI / DCI72, DNG72 DCI / DCI 72Z5.3.1 Cooling Capacity (k
5-12PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.3.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL
5-13PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure VS. Out
iTABLE OF CONTENTSRevision Y07-02Service Manual - DNG DCITable of Contents1. INTRODUCTION ...
5-14PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.3.6 Pressure Curves (Heating – Test Mode)Suction Pressure
5-15PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3.7 Capacity Correction Factor Due to Tubing Length Cooling Heatin
5-16PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.4 DNG80 DCI / DCI 805.4.1 Cooling Capacity (kW)ID COIL EN
5-17PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.4.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING
5-18PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCIDischarge Pressure VS. Outdoor Temp'.100012501500175020
5-19PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCISuction Pressure VS.Outdoor Temp'.200300400500600700800900100011
5-20PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.4.7 Capacity Correction Factor Due to Tubing Length Cooli
6-1AIRFLOW CURVESRevision Y07-02Service Manual - DNG DCI6. AIRFLOW CURVES6.1 Model: DNG 50 DCI6.2 Model: DNG 60 DCICONTENT
6-2AIRFLOW CURVES Revision Y07-02 Service Manual - DNG DCI6.3 Model: DNG 72 DCI6.4 Model: DNG 80 DCICONTENT
6-3AIRFLOW CURVESRevision Y07-02Service Manual - DNG DCI6.5 DNG UNITS RANGE AIR FLOW CORRECTION FACTORS (at nominal rating conditions — Test mode).Ai
1-1INTRODUCTIONRevision Y07-02Service Manual - DNG DCI1. INTRODUCTION1.1 GeneralThe DNG DCI ducted split unit range comprises the following RC (heat
7-1SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCI7. SOUND LEVEL CHARACTERISTICS7.1 Sound Pressure LevelFigure 17.2 Soud Pressur
7-2SOUND LEVEL CHARACTERISTICS Revision Y07-02 Service Manual - DNG DCIDNG 72 DNG 80FAN SPEED LINEHIMELOCONTENT
7-3SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCI7.3 Outdoor units7.4 Sound Pressure Level Spectrum (Measured as Figure 2)DCI 50
7-4SOUND LEVEL CHARACTERISTICS Revision Y07-02 Service Manual - DNG DCIDCI 72 Cooling DCI 72 HeatingDCI 72Z Cooling DCI 72Z HeatingCONTENT
7-5SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCIDCI 80 Cooling DCI 80 HeatingCONTENT
8-1ELECTRICAL DATARevision Y07-02Service Manual - DNG DCI8. ELECTRICAL DATA8.1 Single Phase UnitsModel DNG50 DNG60 DNG72 DNG80 Power Supply 1 PH
9-1WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9. WIRING DIAGRAMS9.1 Indoor Unit: DNG 50 DCI9.2 Indoor Unit: DNG 60 DCICONTENT
9-2WIRING DIAGRAMS Revision Y07-02 Service Manual - DNG DCI9.3 Indoor Unit: DNG 72/80 DCICONTENT
9-3WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9.4 Outdoor Unit: DCI 50/609.4.1 DCI 50/60 for Indoor Power Supply9.4.2 DCI 50/60 for Outd
9-4WIRING DIAGRAMS Revision Y07-02 Service Manual - DNG DCI9.5 Outdoor Unit: DCI 72ZABCPRELLORTNOCUDORETAEHESAB)LANOITPO(9PJABCPRETLIFIMEPMOCN
1-2INTRODUCTIONRevision Y07-02 Service Manual - DNG DCI1.3 Indoor Unit The indoor unit is a low silhouette ducted unit, and can be easily fitted to man
9-5WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9.6 Outdoor Unit: DCI 72/80CONTENT
10-1REFRIGERATION DIAGRAMSRevision Y07-02Service Manual - DNG DCI10. REFRIGERATION DIAGRAMS10.1 Heat Pump Models10.1.1 DNG 50/60/72/80 Cooling mode He
11-1TUBING CONNECTIONSRevision Y07-02Service Manual - DNG DCI11. TUBING CONNECTIONS TUBE (Inch)TORQUE (Nm)¼” ⅜” ½” ⅝” ¾”Flare Nuts15-18 40-45 60-
12-1CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12. CONTROL SYSTEM12.1 General Functions and Operating RulesThe DCI software is fully param
12-2CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCITarget frequency limits as a function of outdoor air temperature (OAT):OAT Range Cooling Mod
12-3CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.1.5.2 Compressor starting control for DCI72/80 Step 1Whenever the compressor starts up,
12-4CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCICompressor Target FrequencyOFAN SpeedRoutinARoutinBRoutinCRoutinDFreq=0 OFF OFF OFF OFF10 ≤
12-5CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.1.9.2 EEV Control for DCI72/72Z/80The target EEV value is the sum of open loop value (OL)
12-6CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.3 Cool ModeNLOAD is calculated according to the difference between actual room temperatur
12-7CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.6 Dry ModeAs long as room temperature is higher then the set point, indoor fan will work
1-3INTRODUCTIONRevision Y07-02Service Manual - DNG DCI1.7 Outdoor UnitThe DNG DCI INV outdoor units can be installed as floor or wall mounted units by
12-8CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.2.2 Indoor Coil Overheating Protection For 72/80ICTICT Trend<-2 -2 -1,0,1 2 >2ICT
12-9CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.3.2 Compressor Overheating Protection for DCI72/80CTTCTT TrendFast DecreasingDecreasing
12-10CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.5.2 Heat Sink Overheating Protection For DCI72/80HSTDelta HST<-2 -2 -1,0,1 2 >2H
12-11CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI► Deicing Operation ProcedureCOMPRVOFANEEVONHEATCOOLONOFFEEVDeicerOpenAnyT1 T2T3 T3T1120Th
12-12CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI► Deicing Operation ProcedureCOMPRVOFANEEVONHEATCOOLONOFF EEVDeicerOpenAnyT1 T2T3
12-13CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIANY0ONNLOADPUMPOFFONOPERLEDOFFOverflowWater LevelNormalBLINKNLOAD isforced to 08 min 8 minO
12-14CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.10 On Unit Controls and Indicators12.10.1 Indoor Unit controller Controls and Indicati
12-15CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.11 Test Mode12.11.1 Entering Test ModeSystem can enter Test mode in two ways:Automatical
12-16CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters - DNGUnitA(DNG50)B(DNG60)C(DNG72)D(DNG80)Cap .Group 3344NomLoad
12-17CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters - PXDUnitA(PXD50)B(PXD60)C(PXD72)D(PXD80)Cap .Group 3 344NomLoa
1-4INTRODUCTIONRevision Y07-02 Service Manual - DNG DCI1.11 Matching Table1.11.1 R410AOUTDOOR UNITSINDOOR UNITSMODELREFRIGER.DNG 50 DCI DNG 60 DCI
12-18CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.12.2 Outdoor Units SW Parameters:Model dependent parameters for DCI50/60# Name Single D
12-19CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters for DCI72ZNo. NameSingleDCI-72Z1 MinFreqC 152 MaxFreqC 703 MinFr
12-20CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters for DCI72/80Compressor Parameters ValueMinOFFTime 3MinOnTime 3Ma
13-1TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13. TROUBLESHOOTING 13.1 Troubleshooting for DCI50/60/72ZWARNING!!!When Power Up – the who
13-2TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 9Unit works in wrong mode (cool instead of
13-3TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.3 Judgment by Indoor/Outdoor Unit DiagnosticsEnter diagnostics mode - press for five s
13-4TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.1.4.1 Indoor Unit Diagnostics and Corrective ActionsNo. Fault Probable Cause Correcti
13-5TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No. Fault Probable Cause Corrective Action14The outdoor fan does not function correctly.Che
13-6TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No. Fault Probable Cause Corrective Action20No cooling or heating takes place, indoor and
13-7TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.5 Outdoor Unit DiagnositsNo Problem 5 4 3 2 11 OCT is disconnected 0 0 0 0 12 OCT is s
2-1PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2. PRODUCT DATA SHEET2.1 DNG50 DCI Model Indoor Unit DNG 50 DCIModel Outdoor Unit DCI 50
13-8TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.1.6 Judgment by MegaToolMegaTool is a special tool to monitor the system states. Using
13-9TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.8 Precaution, Advise and Notice Items13.1.8.1 High voltage in Outdoor unit controlle
13-10TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2 Troubleshooting for DCI72/80WARNING!!!When Power Up – the whole outdoor unit contr
13-11TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 7Outdoor unit display board and leds are off
13-12TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 21Other home appliances operation is fault
13-13TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Problem 543211OCT bad 000012CTT bad 000103HST bad 000114OAT bad 001005OMT bad 001016RGT
13-14TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.3.2 Outdoor fault corrective actionsNo Fault Name Probable Cause Corrective Actio
13-15TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Fault Name Probable Cause Corrective Action18 No communication A No signals in line A
13-16TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.4 Fault Code for Indoor unitPressing Mode button for long will activate diagnostic
13-17TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.2.4.1 Indoor unit diagnostics and corrective actionsNo.Fault Probable Cause Corrective
2-2PRODUCT DATA SHEETRevision Y07-02 Service Manual - DNG DCI2.2 DNG60 DCI Model Indoor Unit DNG 60 DCIModel Outdoor Unit DCI 60 R410AInstallation Met
13-18TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.5.4 Checking the Outdoor Fan MotorCheck FAN-Power and FAN-Halls connections - Repa
13-19TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.2.5.10 Checking for electromagnetic interferance (EMC problems)EMC troubles to the A/C
13-20TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.6.3 Advise:Open the Outdoor unit controller cover only after one minute from power