Electra DUO 38 DCI Manuel de service

Naviguer en ligne ou télécharger Manuel de service pour Climatiseurs à système divisé Electra DUO 38 DCI. Electra DUO 38 DCI Service manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 92
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
DNG DC Inverter Series
Indoor Units Outdoor Units
DNG 50 DCI DCI 50
DNG 60 DCI DCI 60
DNG 72 DCI
DCI 72
DCI 72Z
DNG 80 DCI DCI 80
APRIL 2007
REFRIGERANT
R410A
HEAT PUMP
CONTENT
Vue de la page 0
1 2 3 4 5 6 ... 91 92

Résumé du contenu

Page 1 - DNG DC Inverter Series

DNG DC Inverter SeriesIndoor Units Outdoor UnitsDNG 50 DCI DCI 50DNG 60 DCI DCI 60DNG 72 DCIDCI 72DCI 72ZDNG 80 DCI DCI 80APRIL 2007REFRIGERANTR410A

Page 2 - Photos are not contractual

2-3PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2.3 DNG72 DCI Model Indoor Unit DNG 72 DCIModel Outdoor Unit DCI 72 R410AInstallation Meth

Page 3 - Table of Contents

2-4PRODUCT DATA SHEETRevision Y07-02 Service Manual - DNG DCI2.4 DNG72Z DCI Model Indoor Unit DNG 72 DCIModel Outdoor Unit DCI 72 Z R410AInstallation

Page 4 - 1. INTRODUCTION

2-5PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2.5 DNG80 DCI Model Indoor Unit DNG 80 DCIModel Outdoor Unit DCI 80 R410AInstallation Meth

Page 5 - 1.6 Control

3-1RATING CONDITIONS Revision Y07-02Service Manual - DNG DCI3. RATING CONDITIONSStandard conditions in accordance with

Page 6 - 1.10 Inbox Documentation

4-1OUTLINE DIMENSIONSRevision Y07-02Service Manual - DNG DCI4. OUTLINE DIMENSIONS4.1 Indoor Unit: DNG 50, 60, 72, 80Model A B C D E F G H I J K LDNG5

Page 7 - 1.11.1 R410A

4-2OUTLINE DIMENSIONSRevision Y07-02 Service Manual - DNG DCI4.2 Outdoor Unit: DCI 504.3 Outdoor Unit: DCI 60CONTENT

Page 8 - 2. PRODUCT DATA SHEET

4-3OUTLINE DIMENSIONSRevision Y07-02Service Manual - DNG DCI4.4 Outdoor Unit: DCI 72/80CONTENT

Page 9 - 2.2 DNG60 DCI

5-1PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5. PERFORMANCE DATA & PRESSURE CURVES5.1 DNG50 DCI / DCI 505.1.1

Page 10 - 2.3 DNG72 DCI

5-2PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.1.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL

Page 11 - 2.4 DNG72Z DCI

5-3PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.1.5 Pressure Curves (Cooling – Test Mode) Discharge Pressure VS. Out

Page 12 - 2.5 DNG80 DCI

ALIST OF EFFECTIVE PAGESRevision Y07-02Service Manual - DNG DCILIST OF EFFECTIVE PAGESNote: Changes in the pages are indicated by a “Revision#” in th

Page 13 - 3. RATING CONDITIONS

5-4PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.1.6 Pressure Curves (Heating – Test Mode)Suction Pressure V

Page 14 - 4. OUTLINE DIMENSIONS

5-5PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.1.7 Capacity Correction Factor Due to Tubing Length Cooling Heating

Page 15 - Outdoor Unit: DCI 60

5-6PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2 DNG60 DCI / DCI 605.2.1 Cooling Capacity (kW)ID COIL ENT

Page 16 - 4.4 Outdoor Unit: DCI 72/80

5-7PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.2.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING

Page 17 - 5.1 DNG50 DCI / DCI 50

5-8PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure

Page 18 - 5.1.3 Heating

5-9PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.2.6 Pressure Curves (Heating – Test Mode)Suction Pressure VS.Outdoor

Page 19 - (Cooling – Test Mode)

5-10PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.2.7 Capacity Correction Factor Due to Tubing Length Cooli

Page 20 - (Heating – Test Mode)

5-11PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3 DNG72 DCI / DCI72, DNG72 DCI / DCI 72Z5.3.1 Cooling Capacity (k

Page 21 - Capacity Ratio

5-12PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.3.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL

Page 22 - 5.2 DNG60 DCI / DCI 60

5-13PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure VS. Out

Page 23 - 5.2.3 Heating

iTABLE OF CONTENTSRevision Y07-02Service Manual - DNG DCITable of Contents1. INTRODUCTION ...

Page 24

5-14PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.3.6 Pressure Curves (Heating – Test Mode)Suction Pressure

Page 25

5-15PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.3.7 Capacity Correction Factor Due to Tubing Length Cooling Heatin

Page 26

5-16PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.4 DNG80 DCI / DCI 805.4.1 Cooling Capacity (kW)ID COIL EN

Page 27 - 5.3.1 Cooling Capacity (kW)

5-17PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCI5.4.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING

Page 28 - 5.3.3 Heating

5-18PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCIDischarge Pressure VS. Outdoor Temp'.100012501500175020

Page 29

5-19PERFORMANCE DATA & PRESSURE CURVESRevision Y07-02Service Manual - DNG DCISuction Pressure VS.Outdoor Temp'.200300400500600700800900100011

Page 30

5-20PERFORMANCE DATA & PRESSURE CURVES Revision Y07-02 Service Manual - DNG DCI5.4.7 Capacity Correction Factor Due to Tubing Length Cooli

Page 31

6-1AIRFLOW CURVESRevision Y07-02Service Manual - DNG DCI6. AIRFLOW CURVES6.1 Model: DNG 50 DCI6.2 Model: DNG 60 DCICONTENT

Page 32 - 5.4 DNG80 DCI / DCI 80

6-2AIRFLOW CURVES Revision Y07-02 Service Manual - DNG DCI6.3 Model: DNG 72 DCI6.4 Model: DNG 80 DCICONTENT

Page 33 - 5.4.3 Heating

6-3AIRFLOW CURVESRevision Y07-02Service Manual - DNG DCI6.5 DNG UNITS RANGE AIR FLOW CORRECTION FACTORS (at nominal rating conditions — Test mode).Ai

Page 34

1-1INTRODUCTIONRevision Y07-02Service Manual - DNG DCI1. INTRODUCTION1.1 GeneralThe DNG DCI ducted split unit range comprises the following RC (heat

Page 35

7-1SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCI7. SOUND LEVEL CHARACTERISTICS7.1 Sound Pressure LevelFigure 17.2 Soud Pressur

Page 36

7-2SOUND LEVEL CHARACTERISTICS Revision Y07-02 Service Manual - DNG DCIDNG 72 DNG 80FAN SPEED LINEHIMELOCONTENT

Page 37 - 6. AIRFLOW CURVES

7-3SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCI7.3 Outdoor units7.4 Sound Pressure Level Spectrum (Measured as Figure 2)DCI 50

Page 38 - 6.4 Model: DNG 80 DCI

7-4SOUND LEVEL CHARACTERISTICS Revision Y07-02 Service Manual - DNG DCIDCI 72 Cooling DCI 72 HeatingDCI 72Z Cooling DCI 72Z HeatingCONTENT

Page 39 - AIRFLOW CURVES

7-5SOUND LEVEL CHARACTERISTICSRevision Y07-02Service Manual - DNG DCIDCI 80 Cooling DCI 80 HeatingCONTENT

Page 40 - 7.1 Sound Pressure Level

8-1ELECTRICAL DATARevision Y07-02Service Manual - DNG DCI8. ELECTRICAL DATA8.1 Single Phase UnitsModel DNG50 DNG60 DNG72 DNG80 Power Supply 1 PH

Page 41 - FAN SPEED LINE

9-1WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9. WIRING DIAGRAMS9.1 Indoor Unit: DNG 50 DCI9.2 Indoor Unit: DNG 60 DCICONTENT

Page 42 - 7.3 Outdoor units

9-2WIRING DIAGRAMS Revision Y07-02 Service Manual - DNG DCI9.3 Indoor Unit: DNG 72/80 DCICONTENT

Page 43 - DCI 72 Cooling DCI 72 Heating

9-3WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9.4 Outdoor Unit: DCI 50/609.4.1 DCI 50/60 for Indoor Power Supply9.4.2 DCI 50/60 for Outd

Page 44 - DCI 80 Cooling DCI 80 Heating

9-4WIRING DIAGRAMS Revision Y07-02 Service Manual - DNG DCI9.5 Outdoor Unit: DCI 72ZABCPRELLORTNOCUDORETAEHESAB)LANOITPO(9PJABCPRETLIFIMEPMOCN

Page 45 - 8. ELECTRICAL DATA

1-2INTRODUCTIONRevision Y07-02 Service Manual - DNG DCI1.3 Indoor Unit The indoor unit is a low silhouette ducted unit, and can be easily fitted to man

Page 46 - 9. WIRING DIAGRAMS

9-5WIRING DIAGRAMSRevision Y07-02Service Manual - DNG DCI9.6 Outdoor Unit: DCI 72/80CONTENT

Page 47 - WIRING DIAGRAMS

10-1REFRIGERATION DIAGRAMSRevision Y07-02Service Manual - DNG DCI10. REFRIGERATION DIAGRAMS10.1 Heat Pump Models10.1.1 DNG 50/60/72/80 Cooling mode He

Page 48 - OUTDOOR UNIT CIRCUIT DIAGRAM

11-1TUBING CONNECTIONSRevision Y07-02Service Manual - DNG DCI11. TUBING CONNECTIONS TUBE (Inch)TORQUE (Nm)¼” ⅜” ½” ⅝” ¾”Flare Nuts15-18 40-45 60-

Page 49 - ABCPRELLORTNOCUDO

12-1CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12. CONTROL SYSTEM12.1 General Functions and Operating RulesThe DCI software is fully param

Page 50 - 9.6 Outdoor Unit: DCI 72/80

12-2CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCITarget frequency limits as a function of outdoor air temperature (OAT):OAT Range Cooling Mod

Page 51 - 10. REFRIGERATION DIAGRAMS

12-3CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.1.5.2 Compressor starting control for DCI72/80 Step 1Whenever the compressor starts up,

Page 52 - ¼” ⅜” ½” ⅝” ¾”

12-4CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCICompressor Target FrequencyOFAN SpeedRoutinARoutinBRoutinCRoutinDFreq=0 OFF OFF OFF OFF10 ≤

Page 53 - 12. CONTROL SYSTEM

12-5CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.1.9.2 EEV Control for DCI72/72Z/80The target EEV value is the sum of open loop value (OL)

Page 54

12-6CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.3 Cool ModeNLOAD is calculated according to the difference between actual room temperatur

Page 55 - Step 3

12-7CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.6 Dry ModeAs long as room temperature is higher then the set point, indoor fan will work

Page 56 - OFAN State

1-3INTRODUCTIONRevision Y07-02Service Manual - DNG DCI1.7 Outdoor UnitThe DNG DCI INV outdoor units can be installed as floor or wall mounted units by

Page 57 - 12.2 Fan Mode

12-8CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.2.2 Indoor Coil Overheating Protection For 72/80ICTICT Trend<-2 -2 -1,0,1 2 >2ICT

Page 58 - 12.5 Auto Cool/Heat Mode

12-9CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.3.2 Compressor Overheating Protection for DCI72/80CTTCTT TrendFast DecreasingDecreasing

Page 59 - 12.7 Protections

12-10CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.7.5.2 Heat Sink Overheating Protection For DCI72/80HSTDelta HST<-2 -2 -1,0,1 2 >2H

Page 60

12-11CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI► Deicing Operation ProcedureCOMPRVOFANEEVONHEATCOOLONOFFEEVDeicerOpenAnyT1 T2T3 T3T1120Th

Page 61 - CONTROL SYSTEM

12-12CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI► Deicing Operation ProcedureCOMPRVOFANEEVONHEATCOOLONOFF EEVDeicerOpenAnyT1 T2T3

Page 62

12-13CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIANY0ONNLOADPUMPOFFONOPERLEDOFFOverflowWater LevelNormalBLINKNLOAD isforced to 08 min 8 minO

Page 63

12-14CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.10 On Unit Controls and Indicators12.10.1 Indoor Unit controller Controls and Indicati

Page 64

12-15CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.11 Test Mode12.11.1 Entering Test ModeSystem can enter Test mode in two ways:Automatical

Page 65 - 12.8 Indoor Unit Dry Contact

12-16CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters - DNGUnitA(DNG50)B(DNG60)C(DNG72)D(DNG80)Cap .Group 3344NomLoad

Page 66

12-17CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters - PXDUnitA(PXD50)B(PXD60)C(PXD72)D(PXD80)Cap .Group 3 344NomLoa

Page 67 - 12.12 SW Parameters

1-4INTRODUCTIONRevision Y07-02 Service Manual - DNG DCI1.11 Matching Table1.11.1 R410AOUTDOOR UNITSINDOOR UNITSMODELREFRIGER.DNG 50 DCI DNG 60 DCI

Page 68 - Service Manual - DNG DCI

12-18CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCI12.12.2 Outdoor Units SW Parameters:Model dependent parameters for DCI50/60# Name Single D

Page 69

12-19CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters for DCI72ZNo. NameSingleDCI-72Z1 MinFreqC 152 MaxFreqC 703 MinFr

Page 70

12-20CONTROL SYSTEMRevision Y07-02Service Manual - DNG DCIModel dependent parameters for DCI72/80Compressor Parameters ValueMinOFFTime 3MinOnTime 3Ma

Page 71

13-1TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13. TROUBLESHOOTING 13.1 Troubleshooting for DCI50/60/72ZWARNING!!!When Power Up – the who

Page 72

13-2TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 9Unit works in wrong mode (cool instead of

Page 73 - 13. TROUBLESHOOTING

13-3TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.3 Judgment by Indoor/Outdoor Unit DiagnosticsEnter diagnostics mode - press for five s

Page 74 - TROUBLESHOOTING

13-4TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.1.4.1 Indoor Unit Diagnostics and Corrective ActionsNo. Fault Probable Cause Correcti

Page 75

13-5TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No. Fault Probable Cause Corrective Action14The outdoor fan does not function correctly.Che

Page 76

13-6TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No. Fault Probable Cause Corrective Action20No cooling or heating takes place, indoor and

Page 77

13-7TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.5 Outdoor Unit DiagnositsNo Problem 5 4 3 2 11 OCT is disconnected 0 0 0 0 12 OCT is s

Page 78

2-1PRODUCT DATA SHEETRevision Y07-02Service Manual - DNG DCI2. PRODUCT DATA SHEET2.1 DNG50 DCI Model Indoor Unit DNG 50 DCIModel Outdoor Unit DCI 50

Page 79

13-8TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.1.6 Judgment by MegaToolMegaTool is a special tool to monitor the system states. Using

Page 80 - 13.1.6 Judgment by MegaTool

13-9TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.1.8 Precaution, Advise and Notice Items13.1.8.1 High voltage in Outdoor unit controlle

Page 81

13-10TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2 Troubleshooting for DCI72/80WARNING!!!When Power Up – the whole outdoor unit contr

Page 82

13-11TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 7Outdoor unit display board and leds are off

Page 83

13-12TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI No Symptom Probable Cause Corrective Action 21Other home appliances operation is fault

Page 84

13-13TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Problem 543211OCT bad 000012CTT bad 000103HST bad 000114OAT bad 001005OMT bad 001016RGT

Page 85

13-14TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.3.2 Outdoor fault corrective actionsNo Fault Name Probable Cause Corrective Actio

Page 86

13-15TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI No Fault Name Probable Cause Corrective Action18 No communication A No signals in line A

Page 87

13-16TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.4 Fault Code for Indoor unitPressing Mode button for long will activate diagnostic

Page 88

13-17TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.2.4.1 Indoor unit diagnostics and corrective actionsNo.Fault Probable Cause Corrective

Page 89

2-2PRODUCT DATA SHEETRevision Y07-02 Service Manual - DNG DCI2.2 DNG60 DCI Model Indoor Unit DNG 60 DCIModel Outdoor Unit DCI 60 R410AInstallation Met

Page 90

13-18TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.5.4 Checking the Outdoor Fan MotorCheck FAN-Power and FAN-Halls connections - Repa

Page 91

13-19TROUBLESHOOTINGRevision Y07-02Service Manual - DNG DCI 13.2.5.10 Checking for electromagnetic interferance (EMC problems)EMC troubles to the A/C

Page 92

13-20TROUBLESHOOTING Revision Y07-02 Service Manual - DNG DCI 13.2.6.3 Advise:Open the Outdoor unit controller cover only after one minute from power